Training in Electrical logo
Electrical Training Courses in Nottingham - 7 Days a Week
01157 950 431
info@traininginelectrical.co.uk

Maximum Zs Values and fuse standards to BS7671

13 October 2012


Amendment 1 of BS 7671:2008 contains some important changes concerning new fuse standards which took effect in March 2010. These changes can be seen in the maximum earth fault loop impedance (Zs) values in Tables 41.2 and 41.4. (Table 41.3 concerns circuit-breakers) The new fuse standards are:

(However, fuses complying with these withdrawn standards will be found in existing electrical installations for some years to come.)

Having noted these changes, we are provided with a convenient opportunity to consider how these maximum Zs values in Tables 41.2, 41.3 and 41.4 are obtained.

This article will look at the maximum Zs values for BS88-3 fuses in Table 41.4(b) as an example of how these maximum Zs values are obtained.

The formula

The maximum earth loop impedance, Zs values are arrived at using the formula in Regulation 411.4.5:

Zs x Ia = Uo

where:

Zs = the earth fault loop impedance in ohms

Ia = the current in amps which causes the protective device to operate within the time specified in Table 41.1 (or, if appropriate, within the 5 second disconnection time specified in Regulation 411.3.2.3 for TN systems).

Where an RCD is used, the current Ia is the rated residual operating current which provides disconnection within the time specified in Table 41.1 (or, if appropriate, within the 5 second disconnection time specified in Regulation 411.3.2.3 for TN systems).

U0 = the nominal voltage to Earth in volts (ie. 230 V for standard a.c. single-phase and three-phase circuits)

Appendix 3

The value of Ia can be obtained by reference to the appropriate time/current characteristic of protective devices and RCDs in Appendix 3 of BS 7671.

Example of 20A BS88-3 fuses

Let us assume we have a 230V, TN, a.c. system with overcurrent protection provided by 20A BS 88-3 fuses for a final circuit not exceeding 32 A.

Table 41.1 requires that disconnection of the circuit takes place within a maximum time of 0.4 seconds.

To calculate the maximum earth fault loop impedance Zs which will ensure that 20A BS 88-3 fuses will disconnect the circuit within 0.4 seconds, we must use the formula in Regulation 411.4.5 shown above, but transpose it to make

U0 the subject. This gives:

Uo

Zs = Ia

U0 = 230V.

To obtain Ia, we turn to Fig. 3A1 in Appendix 3, which gives the time-current characteristics for BS 88-3 fuses.

The line representing the 20A fuse gives us the value of current but it’s much easier to use the table at the top right of the page. (If you need the practice, you could use the 20A line to confirm the value obtained in the table) From this table we can see that the value of current which causes a 20A BS 88-3 fuse to operate within 0.4 seconds is 113 A. Turning again to the formula:

Uo

Zs = Ia

230

Zs = 113

Zs = 2.04 ohms.

As the required disconnection time is 0.4 seconds, we turn to Table 41.2(b). Here we find that the maximum Zs value for 20 A BS 88-3 fuses is 2.04 ohms.

BS 3036 and BS 1362

The other fuse standards in Tables 41.2 and 41.4 – BS 3036 and BS 1362 – rem

Share this article